Table 27: Output signals, G2.3
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.3.12
Output frequency
limit 2 supervision
0
2
0
346
0 = No limit
1 = Low limit
supervision
2 = High limit
supervision
P2.3.13
Output frequency
limit 2; Supervi-
sion value
0.00
320.00
Hz
0.00
347
P2.3.14
Torque limit
supervision func-
tion
0
2
0
348
0 = No
1 = Low limit
2 = High limit
P2.3.15
Torque limit
supervision value
-300.0
300.0
%
0.0
349
P2.3.16
Reference limit
supervision func-
tion
0
2
0
350
0 = No
1 = Low limit
2 = High limit
P2.3.17
Reference limit
supervision value
0.0
100.0
%
0.0
351
P2.3.18
External brake
Off-delay
0.0
100.0
s
0.5
352
P2.3.19
External brake
On-delay
0.0
100.0
s
1.5
353
P2.3.20
Frequency con-
verter tempera-
ture limit supervi-
sion
0
2
0
354
0 = No
1 = Low limit
2 = High limit
P2.3.21
Frequency con-
verter tempera-
ture limit value
-10
100
°C
40
355
P2.3.22 * Analogue output 2
scaling
0.1
E.10
0.1
471
TTF programming
method used. See
P2.3.23 * Analogue output 2
function
0
8
4
472
As parameter 2.3.2