412 REVERSE * 67 (2.2.7.4, 2.2.6.11)
Contact open: Direction forward
Contact closed: Direction reverse
This command is active when Start signal 2 (ID404) is used for other purposes.
413 JOGGING SPEED * 67 (2.2.7.16, 2.2.6.12)
Contact closed: Jogging speed selected for frequency reference
See parameter ID124.
Default programming: A.4.
414 FAULT RESET * 67 (2.2.7.10, 2.2.6.13)
CLOSED = Resets all active faults.
415 ACCELERATION /DECELERATION PROHIBITED * 67 (2.2.7.14, 2.2.6.14)
No acceleration or deceleration is possible until the contact is open.
416 DC-BRAKING * 67 (2.2.7.15, 2.2.6.15)
Contact closed:In STOP mode, the DC braking operates until the contact is opened.
See ID1080.
417 MOTOR POTENTIOMETER DOWN * 67 (2.2.7.8, 2.2.6.16)
Contact closed: Motor potentiometer reference DECREASES until the contact is opened.
418 MOTOR POTENTIOMETER UP * 67 (2.2.7.9, 2.2.6.17)
Contact closed:Motor potentiometer reference INCREASES until the contact is opened.
419 PRESET SPEED * 16 (2.2.7.5)
420 PRESET SPEED * 26 (2.2.7.6)
421 PRESET SPEED * 36 (2.2.7.7)
Digital input selections for activating the preset speeds.
422 AI1/AI2 SELECTION * 6 (2.2.7.17)
With value 14 selected for parameter ID117, this parameter allows you to select either AI1 or
AI2 signal for the frequency reference.
423 START A SIGNAL * 7 (2.2.6.1)
Start command from control place A.
VACON · 292
PARAMETER DESCRIPTIONS
8
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205