Table 65: Limit settings (Control keypad: Menu M2 -> G2.3.4)
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.3.4.1
Output frequency
limit 1 supervision
0
3
0
315
0 = No supervision
1 = Low limit
supervision
2 = High limit
supervision
3 = Brake-on con-
trol
P2.3.4.2
Output frequency
limit 1; Supervised
value
0.00
320.00
Hz
0.00
316
P2.3.4.3
Output frequency
limit 2 supervision
0
4
0
346
0 = No supervision
1 = Low limit
supervision
2 = High limit
supervision
3 = Brake-off con-
trol
4 = Brake on/off
control
P2.3.4.4
Output frequency
limit 2; Supervised
value
0.00
320.00
Hz
0.00
347
P2.3.4.5
Torque limit
supervision
0
3
0
348
0 = No supervision
1 = Low limit
supervision
2 = High limit
supervision
3 = Brake-off con-
trol
P2.3.4.6
Torque limit
supervision value
-300.0
300.0
%
100.0
349
For brake control
absolute values
are used.
P2.3.4.7
Reference limit
supervision
0
2
0
350
0 = No supervision
1 = Low limit
2 = High limit
P2.3.4.8
Reference limit
supervision value
0.0
100.0
%
0.0
351
0.0 = Min fre-
quency
100.0 = Max fre-
quency