Table 10: Motor control parameters, G2.6
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.6.7 *
U/f curve midpoint
voltage
0.00
100.00
%
100.00
605
If the value of
P2.6.3 is program-
mable, this param-
eter gives the mid-
dle point frequency
of the curve.
P2.6.8 *
Output voltage at
zero frequency
0.00
40.00
%
Varies
606
This parameter
gives the zero fre-
quency voltage of
the U/f curve. The
default value is dif-
ferent for different
unit sizes.
P2.6.9
Switching fre-
quency
1.0
Varies
kHz
Varies
601
If you increase the
switching fre-
quency, the
capacity of the AC
drive reduces. To
reduce capacitive
currents in the
motor cable, when
the cable is long,
we recommend
that you use a low
switching fre-
quency. To reduce
the motor noise,
use a high switch-
ing frequency.
P2.6.10
Overvoltage con-
troller
0
2
1
607
0 = Not used
1 = Used (no
ramping)
2 = Used (ramping
P2.6.11
Undervoltage con-
troller
0
1
1
608
0 = Not used
1 = Used
P2.6.12
Load drooping
0.00
100.00
%
0.00
620
The function ena-
bles a speed drop
as a function of
load. The load
drooping is given
as a percentage of
the nominal speed
at a nominal load.