Table 66: Analogue output 1 (Control keypad: Menu M2 -> G2.3.5)
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.3.5.6
Analogue output 1
scale
10
1000
%
100
311
P2.3.5.7
Analogue output 1
offset
-100.00
100.00
%
0.00
375
* = Use TTF method to program these parameters.
Table 67: Analogue output 2 (Control keypad: Menu M2 -> G2.3.6)
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.3.6.1 * Analogue output 2
signal selection
0.1
E.10
0.1
471
TTF programming
method used. See
P2.3.6.2
Analogue output 2
function
0
15
4
472
See P2.3.5.2
P2.3.6.3
Analogue output 2
filter time
0.00
10.00
s
1.00
473
0 = No filtering
P2.3.6.4
Analogue output 2
inversion
0
1
0
474
0 = Not inverted
1 = Inverted
P2.3.6.5
Analogue output 2
minimum
0
1
0
475
0 = 0 mA (0 V)
1 = 4 mA (2 V)
P2.3.6.6
Analogue output 2
scale
10
1000
%
100
476
P2.3.6.7
Analogue output 2
offset
-100.00
100.00
%
0.00
477
* = Use TTF method to program these parameters.
MULTI-PURPOSE CONTROL APPLICATION
VACON · 163