405 EXTERNAL FAULT (CLOSE) * 67 (2.2.7.11, 2.2.6.4)
Contact closed:Fault (F51) is displayed and motor stopped.
406 EXTERNAL FAULT (OPEN) * 67 (2.2.7.12, 2.2.6.5)
Contact open:Fault (F51) is displayed and motor stopped.
407 RUN ENABLE * 67 (2.2.7.3, 2.2.6.6)
When the contact is OPEN, the start of the motor is disabled.
When the contact is CLOSED, the start of the motor is enabled.
To stop, the drive obeys the value of parameter ID506. The follower drive will always coast to
stop.
408 ACCELERATION/DECELERATION TIME SELECTION * 67 (2.2.7.13, 2.2.6.7)
When the contact is OPEN, the Acceleration/Deceleration time 1 selected
When the contact is CLOSED, the Acceleration/Deceleration time 2 selected
Set Acceleration/Deceleration times with parameters ID103 and ID104 and the alternative
ramp times with ID502 and ID503.
409 CONTROL FROM I/O TERMINAL * 67 (2.2.7.18, 2.2.6.8)
Contact closed:Force control place to I/O terminal
This input has priority over parameters ID410 and ID411.
410 CONTROL FROM KEYPAD * 67 (2.2.7.19, 2.2.6.9)
Contact closed:Force control place to keypad
This input has priority over parameter ID411 but preceded in priority by ID409.
411 CONTROL FROM FIELDBUS * 67 (2.2.7.20, 2.2.6.10)
Contact closed:Force control place to fieldbus
This input is preceded in priority by parameters ID409 and ID410.
NOTE!
When the control place is forced to change the values of Start/Stop, Direction and
Reference valid in the respective control place are used.
The value of parameter ID125 (Keypad Control Place) does not change.
When the input opens the control place is selected according to keypad control parameter
ID125.
PARAMETER DESCRIPTIONS
VACON · 291
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]
8