Table 38: Drive control parameters, G2.4
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.4.10
Frequency to start
DC braking during
ramp stop
0.10
10.00
Hz
1.50
515
P2.4.11
DC braking time
at start
0.00
600.00
s
0.00
516
0 = DC brake is off
at start
P2.4.12 *
Flux brake
0
1
0
520
0 = Off
0 = On
P2.4.13
Flux braking cur-
rent
0.00
I
L
A
I
H
519
5.4.6
PROHIBIT FREQUENCY PARAMETERS (CONTROL KEYPAD: MENU M2 -> G2.5)
Table 39: Prohibit frequency parameters, G2.5
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.5.1
Prohibit frequency
range 1 low limit
-1.00
320.00
Hz
0.00
509
0 = Not used
P2.5.2
Prohibit frequency
range 1 high limit
0.00
320.00
Hz
0.00
510
0 = Not used
P2.5.3
Prohibit frequency
range 2 low limit
0.00
320.00
Hz
0.00
511
0 = Not used
P2.5.4
Prohibit frequency
range 2 high limit
0.00
320.00
Hz
0.00
512
0 = Not used
P2.5.5
Prohibit frequency
range 3 low limit
0.00
320.00
Hz
0.00
513
0 = Not used
P2.5.6
Prohibit frequency
range 3 high limit
0.00
320.00
Hz
0.00
514
0 = Not used
P2.5.7
Prohibit acc./dec.
ramp
0.1
10.0
x
1.0
518
VACON · 116