Table 45: Monitoring values, NXP drives
Index
Monitoring value
Unit
ID
Description
V1.22.6
Motor Current to FB
A
45
Motor current (drive independent) given with one
decimal point
V1.22.7
DIN StatusWord 1
56
See Table 47 Digital input statuses: ID56 and ID57
V1.22.8
DIN StatusWord 2
57
See Table 47 Digital input statuses: ID56 and ID57
V1.22.9
Warning
74
Last active warning code
V1.22.10
Fault Word1
1172
See Table 48 Fault Word 1, ID1172
V1.22.11
Fault Word2
1173
See Table 49 Fault Word 2, ID1173
V1.22.12
Warning Word1
1174
See Table 50 Warning Word 1, ID1174
V1.23.1
SystemBus System
Status
1601
See Table 51 SystemBus Status Word, ID1601
V1.23.2
Total current
A
83
Total current of the drives in Master Follower sys-
tem.
V1.23.3.1
Motor current D1
A
1616
D1: This value is the current of drive number one
power unit. D2, D3 and D4: Not updated.
V1.23.3.2
Motor current D2
A
1605
D1:This value is the current of drive number two
power unit. D2, D3 and D4: Not updated.
V1.23.3.3
Motor current D3
A
1606
D1:This value is the current of drive number three
power unit. D2, D3 and D4: Not updated.
V1.23.3.4
Motor current D4
A
1607
D1: This value is the current of drive number four
power unit. D2, D3 and D4: Not updated.
V1.23.4.1
StatusWord D1
1615
See Table 52 Follower drive Status Word
V1.23.4.2
StatusWord D2
1602
See Table 52 Follower drive Status Word
V1.23.4.3
StatusWord D3
1603
See Table 52 Follower drive Status Word
V1.23.4.4
StatusWord D4
1604
See Table 52 Follower drive Status Word
Table 46: Digital input statuses: ID15 and ID16
DIN1/DIN2/DIN3 status
DIN4/DIN5/DIN6 status
b0
DIN3
DIN6
b1
DIN2
DIN5
b2
DIN1
DIN4
MULTI-PURPOSE CONTROL APPLICATION
VACON · 135
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]
6