Table 16: Input signals, G2.2
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.2.15
***
Place B Start/Stop
logic selection
0
6
0
363
Logic = 0
Ctrl sgn 1 = Start
forward
Ctrl sgn 2 = Start
reverse
Logic = 1
Ctrl sgn 1 = Start/
Stop
Ctrl sgn 2 = Reverse
Logic = 2
Ctrl sgn 1 = Start/
Stop
Ctrl sgn 2 = Run
enable
Logic = 3
Ctrl sgn 1 = Start
pulse (edge)
Ctrl sgn 2 = Stop
pulse
Logic = 4
Ctrl sgn 1 = Forward
pulse (edge)
Ctrl sgn 2 = Reverse
pulse (edge)
Logic = 5
Ctrl sgn 1 = Start
pulse (edge)
Ctrl sgn 2 = Reverse
pulse
Logic = 6
Ctrl sgn 1 = Start
pulse (edge)
Ctrl sgn 2 = Enable
pulse
P2.2.16
Place A Reference
scaling minimum
value
0.00
320.00
Hz
0.00
303
Selects the fre-
quency that corre-
sponds to the min.
reference signal.
VACON · 52
LOCAL/REMOTE CONTROL APPLICATION