Table 94: Analogue output 1 (Control keypad: Menu M2 -> G2.3.3)
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.3.3.1 * Analogue output 1
signal selection
0.1
E.10
A.1
464
TTF programming
method used. See
P2.3.3.2
Analogue output
function
0
14
1
307
0 = Not used (20
mA / 10 V)
1 = Output freq. (0-
f
max
)
2 = Freq. refer-
ence (0-f
max
)
3 = Motor speed
(0-Motor nominal
speed
4 = Motor current
(0-I
nMotor
)
5 = Motor torque
(0-T
nMotor
)
6 = Motor power
(0-P
nMotor
)
7 = Motor voltage
(0-U
nMotor
)
8 = DC link volt
(0-1000V)
9 = PID controller
ref. value
10 = PID contr.
act.value 1
11 = PID contr.
act.value 2
12 = PID contr.
error value
13 = PID controller
output
14 = PT100 tem-
perature
P2.3.3.3
Analogue output
filter time
0.00
10.00
s
1.00
308
0 = No filtering
P2.3.3.4
Analogue output
inversion
0
1
0
309
0 = Not inverted
1 = Inverted
P2.3.3.5
Analogue output
minimum
0
1
0
310
0 = 0 mA (0 V)
1 = 4 mA (2 V)
P2.3.3.6
Analogue output
scale
10
1000
%
100
311
PUMP AND FAN CONTROL APPLICATION
VACON · 219
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]