6.4.10
FIELDBUS PARAMETERS (CONTROL KEYPAD: MENU M2 ->G2.9)
Table 80: Fieldbus parameters
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.9.1
Fieldbus min
scale
0.00
320.00
Hz
0.00
850
P2.9.2
Fieldbus max
scale
0.00
320.00
Hz
0.00
851
P2.9.3
Fieldbus process
data out 1 selec-
tion
0
10000
1
852
The data that is
sent to fieldbus
with the ID of the
parameter or mon-
itor. The data is
scaled to an
unsigned 16-bit
format according
to the format on
the control panel.
For example, 25.5
on the display
agrees with 255.
P2.9.4
Fieldbus process
data out 2 selec-
tion
0
10000
2
853
Make the selection
of the Process
Data Out with the
parameter ID.
P2.9.5
Fieldbus process
data out 3 selec-
tion
0
10000
45
854
Make the selection
of the Process
Data Out with the
parameter ID.
P2.9.6
Fieldbus process
data out 4 selec-
tion
0
10000
4
855
Make the selection
of the Process
Data Out with the
parameter ID.
P2.9.7
Fieldbus process
data out 5 selec-
tion
0
10000
5
856
Make the selection
of the Process
Data Out with the
parameter ID.
P2.9.8
Fieldbus process
data out 6 selec-
tion
0
10000
6
857
Make the selection
of the Process
Data Out with the
parameter ID.
P2.9.9
Fieldbus process
data out 7 selec-
tion
0
10000
7
858
Make the selection
of the Process
Data Out with the
parameter ID.
MULTI-PURPOSE CONTROL APPLICATION
VACON · 187