Table 35: Basic parameters G2.1
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P1.1.16
Sleep delay
0
3600
s
30
1017
The minimum
quantity of time
during which the
frequency has to
stay below the
sleep level before
the drive stops.
P1.1.17
Wake up level
0.00
100.00
%
25.00
1018
Gives the level for
the PID feedback
value wake-up
supervision. Uses
the set process
units.
P1.1.18
Wake up function
0
1
0
1019
0 = Wake-up at fall
below wake up
level (2.1.17)
1 = Wake-up at
exceeded wake up
level (2.1.17)
P1.1.19
Jogging speed
reference
0.00
P2.1.2
Hz
10.00
124