Table 41: Protections, G2.7
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.7.25
Response to PT100
fault
0
3
0
740
0 = No response
1 = Warning
2 = Fault,stop acc.
to 2.4.7
3 = Fault,stop by
coasting
P2.7.26
PT100 warning
limit
-30.0
200.0
ºC
120.0
741
P2.7.27
PT100 fault limit
-30.0
200.0
ºC
130.0
742