170 FIELDBUS DIN 5 (FBFIXEDCONTROLWORD, BIT 7) 6 (2.3.3.28)
The data from the fieldbus can be led to the digital outputs of the AC drive. See the used
fieldbus manual for more details.
179 SCALING OF MOTORING POWER LIMIT 6 (2.2.6.7)
The motoring power limit is equal to ID1289 if value 0 'Not used' is selected. If any of the
inputs is selected the motoring power limit is scaled between zero and parameter ID1289.
This parameter is available for NXP closed loop control mode only.
Table 114: Selections for parameter ID179
Selection
number
Selection name
Description
0
Not used
1
AI1
2
AI2
3
AI3
4
AI4
5
FB Limit Scaling ID46 (monitor-
ing value)
PARAMETER DESCRIPTIONS
VACON · 249
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]
8