Table 200: Selections for parameter ID1089
Selection
number
Selection name
Description
0
Coasting, follower remains in
control even if master has
stopped at fault
1
Ramping, follower remains in
control even if master has
stopped at fault
2
As master; follower behaves as
master
1090 RESET ENCODER COUNTER 6 (2.2.7.29)
Resets the monitoring values Shaft Angle and Shaft Rounds to zero. See Table 44 Monitoring
The parameter is available for NXP drives only.
1092 MASTER FOLLOWER MODE 26 (2.2.7.31)
Select the digital input to activate the second Master Follower mode selected by parameter
ID1093. The parameter is available for NXP drives only.
1093 MASTER FOLLOWER MODE 2 SELECTION 6 (2.11.7)
Select Master Follower mode 2 that is used when the DI is activated. When Follower is
selected the Run Request command is monitored from Master and all other references are
selectable by parameters.
Table 201: Selections for parameter ID1093
Selection
number
Selection name
Description
0
Single Drive
1
Master
2
Follower
1209 INPUT SWITCH ACKNOWLEDGEMENT 6 (2.2.7.32)
Select the digital input to acknowledge the status of the input switch. The input switch is
normally a switch fuse unit or main contactor with which the power is fed to the drive. If the
input switch acknowledgement is missing, the drive trips at Input switch open fault (F64). The
parameter is available for NXP drives only.