301 DIN3 FUNCTION 12345 (2.17, 2.2.2)
Table 116: Selections for parameter ID301
Selection
number
Selection name
Description
Notes
0
Not used
1
External fault
Closing contact: Fault is shown and respon-
ded to according to ID701.
2
External fault
Opening contact: Fault is shown and respon-
ded to according to ID701 when the input is
not active.
3
Run enable
Contact open: Motor start disabled and the
motor is stopped READY signal is set to
FALSE
Contact closed: Motor start enabled
Application 1
4
Run enable
Contact open: Motor start enabled
Contact closed: Motor start disabled and the
motor is stopped
Applications 2 to 5
4
Acc./Dec time
select.
Contact open: Acceleration/deceleration time
1 selected
When the control place is
forced to change the values
of Start/Stop, Direction and
Reference valid in the
respective control place are
used (reference according to
parameters ID117, ID121 and
ID122).
NOTE!
The value of parameter
ID125 Keypad Control Place
does not change.
When DIN3 opens the control
place is selected according
to parameter 3.1.
Contact closed: Acceleration/deceleration
time 2 selected
5
Closing contact
Force control place to I/O terminal
6
Closing contact
Force control place to keypad
7
Closing contact
Force control place to fieldbus
Applications 2 to 5
8
Reverse
Contact open: Forward
Can be used for reversing if
parameter ID300 value is set
to either 2,3, or 6.
Contact closed: Reverse
Applications 3 to 5
PARAMETER DESCRIPTIONS
VACON · 253
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]
8