363 START/STOP LOGIC SELECTION, PLACE B3 (2.2.15)
Table 139: Selections for parameter ID363
Selection
DIN3
DIN4
DIN5
0
closed contact = start forward
closed contact = start reverse
See Fig. 54.
1
closed contact = startopen
contact = stop
closed contact = reverseopen
contact = forward
See Fig. 55.
2
closed contact = start, open
contact = stop
closed contact = start enabled,
open contact = start disabled and
drive stopped if running
3 *
Can be programmed for
reverse command
closed contact= start pulse
open contact = stop pulse
See Fig. 56.
4 **
closed contact = start forward
(Rising edge required to start)
closed contact = start reverse
(Rising edge required to start)
5 **
closed contact = start (Rising
edge required to start)
open contact = stop
closed contact = reverse
open contact = forward
6 **
closed contact = start (Rising
edge required to start)
open contact = stop
closed contact = start enabled
open contact = start disabled and
drive stopped if running
* = 3-wire connection (pulse control)
** = The selections 4 to 6 are used to exclude the possibility of an unintentional start when,
for example, power is connected, re-connected after a power failure, after a fault reset, after
the drive is stopped by Run Enable (Run Enable = False) or when the control place is
changed. The Start/Stop contact must be opened before the motor can be started.
The selections including the text 'Rising edge required to start' are used to exclude the
possibility of an unintentional start when, for example, power is connected, re-connected
after a power failure, after a fault reset, after the drive is stopped by Run Enable (Run Enable
= False) or when the control place is changed from I/O control. The Start/Stop contact must
be opened before the motor can be started.