Table 85: Basic parameters G2.1
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.1.16
Sleep delay
0
3600
s
30
1017
The minimum
quantity of time
during which the
frequency has to
stay below the
sleep level before
the drive stops.
P2.1.17
Wake up level
0.0
1000.0
%
25.0
1018
Gives the level for
the PID feedback
value wake-up
supervision. Uses
the set process
units.
P2.1.18
Wake up function
0
3
0
1019
0 = Wake-up at fall
below wake up
level (P2.1.17)
1 = Wake-up at
exceeded wake up
level (P2.1.17)
2 = Wake-up at fall
below wake up
level (P3.4/3.5)
3 = Wake-up at
exceeded wake up
level (P3.4/3.5)
P2.1.19
Jogging speed
reference
0.00
P2.1.2
Hz
10.00
124
* = Apply the Terminal to Function method (TTF) to these parameters (see Chapter 8.9
"Terminal to function" (TTF) programming principle).
PUMP AND FAN CONTROL APPLICATION
VACON · 205