Function
Range or value
Accuracy
Critical impulse time
10 ms typically at 0 to 2 x I
set
-
Operate time at 0 to 10 x I
set
Min. = 5 ms
Max. = 15 ms
-
Reset time at 10 x I
set
to 0
Min. = 25 ms
Max. = 35 ms
-
Critical impulse time
2 ms typically at 0 to 10 x I
set
-
Dynamic overreach
< 5% at
t
= 100 ms
-
6.4
Directional residual overcurrent protection, four
steps EF4PTOC
IP14509-1 v8
6.4.1
Identification
M14881-1 v6
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Directional residual overcurrent
protection, four steps
EF4PTOC
4(IN>)
4
alt
4
TEF-REVA V2 EN-US
51N_67N
6.4.2
Functionality
M13667-3 v19
EF4PTOC has an inverse or definite time delay independent for each step.
All IEC and ANSI time-delayed characteristics are available together with an
optional user-defined characteristic.
EF4PTOC can be set to be directional or non-directional independently for each
step.
IDir, UPol and IPol can be independently selected to be either zero sequence or
negative sequence.
A second harmonic blocking can be set individually for each step.
The residual current can be calculated by summing the three-phase currents or
taking the input from the neutral CT.
Section 6
1MRK 505 384-UEN A
Current protection
104
Breaker protection REQ650 2.2 IEC
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...