SealIn = On
All UL <
USealIn<
Any UL <
UsealIn<
t
5 s
AND
3PH
MCBOP
All UL >
UsealIn<
t
60 s
CBCLOSED
BLOCK
AND
TEST
TEST ACTIVE
AND
BlocFuse = Yes
OpMode
AND
t
200 ms
AND
OR
DISCPOS
BLKU
BLKZ
AND
AND
FuseFailDetZeroSeq
UZsIZs OR UNsINs
UZsIZs AND UNsINs
UZsIZs
UNsINs
OptimZsNs
AND
FuseFailDetNegSeq
OR
AND
AND
CurrZeroSeq
CurrNegSeq
a
b
a>b
OR
AND
AND
AND
FuseFailDetDUDI
AND
OpDUDI = On
DeadLineDet1Ph
OR
OR
OR
OR
AND
VoltZeroSeq
VoltNegSeq
t
5 s
AllCurrLow
t
150 ms
intBlock
Fuse failure detection
Main logic
BLKTRIP
AND
t
100 ms
OR
t
20 ms
OR
IEC10000033-2-en.vsd
OR
FusefailStarted
IEC10000033 V2 EN-US
Figure 97:
Simplified logic diagram for fuse failure supervision function, Main
logic
Section 8
1MRK 505 384-UEN A
Secondary system supervision
218
Breaker protection REQ650 2.2 IEC
Technical manual