9.4.4.2
Function block
M13469-3 v4
QCBAY
LR_OFF
LR_LOC
LR_REM
LR_VALID
BL_UPD
BL_CMD
PSTO
UPD_BLKD
CMD_BLKD
LOC
STA
REM
IEC10000048-3-en.vsdx
IEC10000048 V3 EN-US
Figure 122:
QCBAY function block
9.4.4.3
Signals
PID-4086-INPUTSIGNALS v8
Table 157:
QCBAY Input signals
Name
Type
Default
Description
LR_OFF
BOOLEAN
0
External Local/Remote switch is in Off position
LR_LOC
BOOLEAN
0
External Local/Remote switch is in Local position
LR_REM
BOOLEAN
0
External Local/Remote switch is in Remote
position
LR_VALID
BOOLEAN
0
Data representing the L/R switch position is valid
BL_UPD
BOOLEAN
0
Steady signal to block the position updates
BL_CMD
BOOLEAN
0
Steady signal to block the command
PID-4086-OUTPUTSIGNALS v8
Table 158:
QCBAY Output signals
Name
Type
Description
PSTO
INTEGER
Value for the operator place allocation
UPD_BLKD
BOOLEAN
Update of position is blocked
CMD_BLKD
BOOLEAN
Function is blocked for commands
LOC
BOOLEAN
Local operation allowed
STA
BOOLEAN
Station operation allowed
REM
BOOLEAN
Remote operation allowed
9.4.4.4
Settings
PID-4086-SETTINGS v8
Table 159:
QCBAY Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
AllPSTOValid
Priority
No priority
-
-
Priority
Override Priority of originators,
commands from both local, station and
remote are allowed
RemoteIncStation
No
Yes
-
-
No
Both Station and Remote control are
allowed but not Local when local remote
switch is in remote
Section 9
1MRK 505 384-UEN A
Control
274
Breaker protection REQ650 2.2 IEC
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...