user must use a PC and - either the PCM600 Disturbance handling tool - or a FTP
or MMS (over 61850) client. The PC can be connected to the IED front, rear or
remotely via the station bus (Ethernet ports).
Indications (IND)
M12155-87 v5
Indications is a list of signals that were activated during the total recording time of
the disturbance (not time-tagged).
Event recorder (ER)
M12155-89 v5
The event recorder may contain a list of up to 150 time-tagged events, which have
occurred during the disturbance. The information is available via the local HMI or
PCM600.
Event list (EL)
M12155-177 v6
The event list may contain a list of totally 1000 time-tagged events. The list
information is continuously updated when selected binary signals change state. The
oldest data is overwritten. The logged signals may be presented via local HMI or
PCM600.
Trip value recorder (TVR)
M12155-91 v5
The recorded trip values include phasors of selected analog signals before the fault
and during the fault.
Disturbance recorder (DR)
M12155-97 v5
Disturbance recorder records analog and binary signal data before, during and after
the fault.
Settings information
GUID-892F72ED-CC6C-469B-90CA-73E9E1181187 v1
For each disturbance recording, the setting values of the configured components
are read twice; once during the trigger of disturbance record and again during post
processing of the disturbance record.
During post processing of the disturbance record, the header file is updated with a
section called
Settings
.
Settings
has complete setting values of the configured
components that are read during the trigger time. The setting values, runtime status
and the behavior of each component are compared between the trigger and the post
processing time. If there are any differences, then it will be added in the header file
under section
Changed_settings
.
In the HDR file, section tag
Settings
has an attribute tag called
function
which
includes parameters that are grouped based on the function instance. The function
tag has content called
name
which is the function name provided together with the
user-defined name in brackets similar to the HMI.
Status
content will indicate the
runtime status of the function and
beh
content will indicate the IEC61850 behavior
of the components, if supported. Non runtime components will not have
status
and
beh
tag contents.
Parameters of the function are listed as a child tag
Set
with contents
name
,
value
and
unit
:
1MRK 505 384-UEN A
Section 11
Monitoring
Breaker protection REQ650 2.2 IEC
473
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...