Channel number used for the remaining 32 analog signals are numbers in the
private range 64 to 95.
Binary signals, 128-channels: for each channel the user can specify a FUNCTION
TYPE and an INFORMATION NUMBER.
M11874-629 v7
Disturbance upload
All analog and binary signals that are recorded with disturbance recorder can be
reported to the master. The last eight disturbances that are recorded are available
for transfer to the master. A successfully transferred disturbance (acknowledged by
the master) will not be reported to the master again.
When a new disturbance is recorded by the IED a list of available recorded
disturbances will be sent to the master, an updated list of available disturbances can
be sent whenever something has happened to disturbances in this list. For example,
when a disturbance is deleted (by other client, for example, SPA) or when a new
disturbance has been recorded or when the master has uploaded a disturbance.
Deviations from the standard
Information sent in the disturbance upload is specified by the standard; however,
some of the information are adapted to information available in disturbance
recorder in the IED series.
This section describes all data that is not exactly as specified in the standard.
ASDU23
In ‘list of recorded disturbances’ (ASDU23) an information element named SOF
(status of fault) exists. This information element consists of 4 bits and indicates
whether:
•
Bit TP: the protection equipment has tripped during the fault
•
Bit TM: the disturbance data are currently being transmitted
•
Bit TEST: the disturbance data have been recorded during normal operation or
test mode.
•
Bit OTEV: the disturbance data recording has been initiated by another event
than start
The only information that is easily available is test-mode status. The other
information is always set (hard coded) to:
TP
Recorded fault with trip. [1]
TM
Disturbance data waiting for transmission [0]
OTEV
Disturbance data initiated by other events [1]
Another information element in ASDU23 is the FAN (fault number). According to
the standard this is a number that is incremented when a protection function takes
1MRK 505 384-UEN A
Section 14
Station communication
Breaker protection REQ650 2.2 IEC
617
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...