Function block
First LON address in
function block
EVENT:17
1280
EVENT:18
1296
EVENT:19
1312
EVENT:20
1328
Event masks
M15083-78 v4
Event mask for each input can be set individually from Parameter Setting Tool
(PST) under:
Settings/IED settings/ Monitoring / Event Function
or via
parameter setting tool (PST) as follows:
•
No events
•
OnSet, at pick-up of the signal
•
OnReset, at drop-out of the signal
•
OnChange, at both pick-up and drop-out of the signal
•
AutoDetect, the EVENT function makes the reporting decision (reporting
criteria for integers has no semantic, prefer to be set by the user)
Single indication
M15083-123 v3
Directly connected binary IO signal via binary input function block (SMBI) is
always reported on change, no changed detection is done in the EVENT function
block. Other Boolean signals, for example a start or a trip signal from a protection
function is event masked in the EVENT function block.
Double indications
M15083-126 v3
Double indications can only be reported for the first 8 inputs on an EVENT
function block.
•
00 generates an intermediate event with the read status 0
•
01 generates an open event with the read status 1
•
10 generates a close event with the read status 2
•
11 generates an undefined event with the read status 3
Analog value
M15083-135 v4
All analog values are reported cyclic. The reporting interval is taken from the
connected function if there is a limit supervised signal. Otherwise it is taken from
the EVENT function block.
Command handling
M15083-80 v4
Commands are transferred using transparent SPA-bus messages. The transparent
SPA-bus message is an explicit LON message which contains an ASCII character
message following the coding rules of the SPA-bus protocol. The message is sent
using explicit messages with message code 41H and using acknowledged transport
service.
Both the SPA-bus command messages (R or W) and the reply messages (D, A or
N) are sent using the same message code. It is mandatory that one device sends out
1MRK 505 384-UEN A
Section 14
Station communication
Breaker protection REQ650 2.2 IEC
563
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...