9.10.5
Settings
PID-6189-SETTINGS v6
Table 197:
SINGLECMD Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
Steady
Pulsed
-
-
Off
Operation Off / On
9.10.6
Operation principle
M12447-3 v3
Single command, 16 signals (SINGLECMD) function has 16 binary output signals.
The outputs can be individually controlled from a substation automation system or
from the local HMI. Each output signal can be given a name with a maximum of
13 characters in PCM600.
The output signals can be of the types Off, Steady, or Pulse. This configuration
setting is done via the local HMI or PCM600 and is common for the whole
function block. The length of the output pulses are 100 ms. In steady mode,
SINGLECMD function has a memory to remember the output values at power
interruption of the IED. Also a BLOCK input is available used to block the
updating of the outputs.
The output signals, OUT1 to OUT16, are available for configuration to built-in
functions or via the configuration logic circuits to the binary outputs of the IED.
Section 9
1MRK 505 384-UEN A
Control
324
Breaker protection REQ650 2.2 IEC
Technical manual