Function
Range or value
Accuracy
Minimum operate time
(0.000-60.000) s
± 0.2% or ± 45 ms
whichever is greater
Operate time, start at 0 to 2 x U
set
Min. = 15 ms
Max. = 30 ms
-
Reset time, start at 2 x U
set
to 0
Min. = 15 ms
Max. = 30 ms
-
Operate time, start at 0 to 1.2 x U
set
Min. = 20 ms
Max. = 35 ms
-
Reset time, start at 1.2 x U
set
to 0
Min. = 5 ms
Max. = 25 ms
-
Critical impulse time
10 ms typically at 0 to 2 x U
set
-
Impulse margin time
15 ms typically
-
7.4
Loss of voltage check LOVPTUV
SEMOD171453-1 v3
7.4.1
Identification
SEMOD171954-2 v2
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Loss of voltage check
LOVPTUV
-
27
7.4.2
Functionality
SEMOD171457-5 v8
Loss of voltage check (LOVPTUV ) is suitable for use in networks with an
automatic system restoration function. LOVPTUV issues a three-pole trip
command to the circuit breaker, if all three phase voltages fall below the set value
for a time longer than the set time and the circuit breaker remains closed.
The operation of LOVPTUV is supervised by the fuse failure supervision
FUFSPVC.
7.4.3
Function block
SEMOD171785-4 v4
IEC07000039-2-en.vsd
LOVPTUV
U3P*
BLOCK
CBOPEN
VTSU
TRIP
START
IEC07000039 V2 EN-US
Figure 87:
LOVPTUV function block
Section 7
1MRK 505 384-UEN A
Voltage protection
198
Breaker protection REQ650 2.2 IEC
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...