10.14.6
Monitored data
PID-6928-MONITOREDDATA v1
Table 284:
INTCOMP Monitored data
Name
Type
Values (Range)
Unit
Description
INEQUAL
BOOLEAN
-
-
Input value is equal to
the reference value
INHIGH
BOOLEAN
-
-
Input value is higher
than the reference value
INLOW
BOOLEAN
-
-
Input value is lower than
the reference value
10.14.7
Operation principle
GUID-E9C1B863-ACA7-45C0-91F1-A51FE38755FE v2
The comparison can be done in two ways,
•
Between 2 inputs, INPUT and REF
•
Between INPUT and the value set by the user
SetValue
.
The selection of reference value for comparison can be done through setting
RefSource
. If
RefSource
is selected as
Input REF
then the reference value for
comparison is taken from second input signal (REF). If
RefSource
is selected as
Set
Value
then the reference value for comparison is taken from setting (
SetValue
).
The comparison can be done either between absolute values or signed values and it
depends on the setting
EnaAbs
. If
EnaAbs
is selected as
Absolute
then both input
and reference value is converted into absolute values and comparison is done. If
EnaAbs
is selected as
Signed
then the comparison is done without any conversion.
The function has three state outputs high, low and equal to condition. It will check
the following condition and give corresponding outputs.
•
If the input is above the reference value then INHIGH is set HIGH
•
If the input is below the reference value then INLOW is set HIGH
•
If the input is equal to reference value then INEQUAL is set HIGH
1MRK 505 384-UEN A
Section 10
Logic
Breaker protection REQ650 2.2 IEC
385
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...