6.3
Instantaneous residual overcurrent protection
EFPIOC
IP14508-1 v3
6.3.1
Identification
M14887-1 v4
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Instantaneous residual overcurrent
protection
EFPIOC
IN>>
IEF V1 EN-US
50N
6.3.2
Functionality
M12701-3 v16
The Instantaneous residual overcurrent protection (EFPIOC) has a low transient
overreach and short tripping times to allow the use for instantaneous earth-fault
protection, with the reach limited to less than the typical eighty percent of the line
at minimum source impedance. EFPIOC is configured to measure the residual
current from the three-phase current inputs and can be configured to measure the
current from a separate current input.
6.3.3
Function block
M12614-3 v6
EFPIOC
I3P*
BLOCK
BLKAR
ENMULT
TRIP
IEC06000269-3-en.vsdx
IEC06000269 V3 EN-US
Figure 39:
EFPIOC function block
6.3.4
Signals
IP11448-1 v2
PID-6915-INPUTSIGNALS v4
Table 46:
EFPIOC Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Three phase currents
BLOCK
BOOLEAN
0
Block of function
BLKAR
BOOLEAN
0
Block input for auto reclose
ENMULT
BOOLEAN
0
Enable current multiplier
1MRK 505 384-UEN A
Section 6
Current protection
Breaker protection REQ650 2.2 IEC
101
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...