10.14.2
Functionality
GUID-A93564FA-0017-4939-A9C1-095DA0FD9832 v1
The function gives the possibility to monitor the level of integer values in the
system relative to each other or to a fixed value. It is a basic arithmetic function
that can be used for monitoring, supervision, interlocking and other logics.
10.14.3
Function block
GUID-EB28F45B-B1D0-452F-98B4-F96D7FA34069 v1
INTCOMP
INPUT
REF
INEQUAL
INHIGH
INLOW
IEC15000052-1-en.vsdx
IEC15000052 V1 EN-US
10.14.4
Signals
PID-6928-INPUTSIGNALS v2
Table 281:
INTCOMP Input signals
Name
Type
Default
Description
INPUT
INTEGER
0
Input value to be compared with reference value
REF
INTEGER
0
Reference value to be compared with input value
PID-6928-OUTPUTSIGNALS v2
Table 282:
INTCOMP Output signals
Name
Type
Description
INEQUAL
BOOLEAN
Input value is equal to the reference value
INHIGH
BOOLEAN
Input value is higher than the reference value
INLOW
BOOLEAN
Input value is lower than the reference value
10.14.5
Settings
PID-6928-SETTINGS v2
Table 283:
INTCOMP Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
EnaAbs
Signed
Absolute
-
-
Signed
Selection for absolute or signed
comparison
RefSource
Set Value
Input REF
-
-
Set Value
Selection for reference value either input
or setting
SetValue
-2000000000 -
2000000000
-
1
100
Set value for reference
Section 10
1MRK 505 384-UEN A
Logic
384
Breaker protection REQ650 2.2 IEC
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...