10.7.9.3
Settings
PID-6976-SETTINGS v1
Table 254:
TIMERSET Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off/On
t
0.000 - 90000.000
s
0.001
0.000
Delay for settable timer n
10.7.9.4
Technical data
GUID-C6C98FE0-F559-45EE-B853-464516775417 v2
Table 255:
Number of TIMERSET instances
Logic block
Quantity with cycle time Range or Value
Accuracy
3 ms
8 ms
100 ms
TIMERSET
15
15
30
(0.000–90000.000) s
±0.5% ±10 ms
10.7.10
Exclusive OR function block XOR
IP11018-1 v2
M11477-3 v4
The exclusive OR function (XOR) is used to generate combinatory expressions
with boolean variables. XOR has two inputs and two outputs. One of the outputs is
inverted. The output signal OUT is 1 if the input signals are different and 0 if they
are the same.
Table 256:
Truth table for XOR function block
INPUT1
INPUT2
OUT
NOUT
0
0
0
1
0
1
1
0
1
0
1
0
1
1
0
1
10.7.10.1
Function block
M11476-3 v1
IEC04000409-2-en.vsd
XOR
INPUT1
INPUT2
OUT
NOUT
IEC04000409 V2 EN-US
Figure 179:
XOR function block
Section 10
1MRK 505 384-UEN A
Logic
364
Breaker protection REQ650 2.2 IEC
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...