7.4.4
Signals
PID-3519-INPUTSIGNALS v6
Table 116:
LOVPTUV Input signals
Name
Type
Default
Description
U3P
GROUP
SIGNAL
-
Voltage connection
BLOCK
BOOLEAN
0
Block the all outputs
CBOPEN
BOOLEAN
0
Circuit breaker open
VTSU
BOOLEAN
0
Block from voltage circuit supervision
PID-3519-OUTPUTSIGNALS v6
Table 117:
LOVPTUV Output signals
Name
Type
Description
TRIP
BOOLEAN
Trip signal
START
BOOLEAN
Start signal
7.4.5
Settings
PID-3519-SETTINGS v6
Table 118:
LOVPTUV Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off/On
UPE
1 - 100
%UB
1
70
Operate voltage in % of base voltage
UBase
tTrip
0.000 - 60.000
s
0.001
7.000
Operate time delay
Table 119:
LOVPTUV Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
tPulse
0.050 - 60.000
s
0.001
0.150
Duration of TRIP pulse
tBlock
0.000 - 60.000
s
0.001
5.000
Time delay to block when all 3ph
voltages are not low
tRestore
0.000 - 60.000
s
0.001
3.000
Time delay for enable the function after
restoration
Table 120:
LOVPTUV Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base
Value groups
1MRK 505 384-UEN A
Section 7
Voltage protection
Breaker protection REQ650 2.2 IEC
199
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...