Only characters A - Z, a - z and 0 - 9 should be used in user names
and passwords.
The maximum of characters in a password is 18.
At least one user must be included in the UserAdministrator group
to be able to write users, created in PCM600, to IED.
SEMOD176296-5 v9
At delivery the default user is the SuperUser. No Log on is required to operate the
IED until a user has been created with the IED User Management..
Once a user is created and downloaded to the IED, that user can perform a Log on,
introducing the password assigned in the tool.
If there is no user created, an attempt to log on will display a message box: “No
user defined!”
If one user leaves the IED without logging off, then after the timeout (set in
Main
menu/Settings/General Settings/HMI/Screen/Display Timeout
) elapses, the IED
returns to Guest state, when only reading is possible. The display time out is set to
10 minutes at delivery.
If there are one or more users created with the IED User Management and
downloaded into the IED, then, when a user intentionally attempts a Log on or
when the user attempts to perform an operation that is password protected, the Log
on window will appear.
The cursor is focused on the User identity field, so upon pressing the
key, the
user can change the user name, by browsing the list of users, with the “up” and
“down” arrows. After choosing the right user name, the user must press the “E”
key again. When it comes to password, upon pressing the
key, the following
character will show up: “$”. After all the letters are introduced (passwords are case
sensitive) choose OK and press the
key again.
If everything is alright at a voluntary Log on, the local HMI returns to the
Authorization screen. If the Log on is OK, when required to change for example a
password protected setting, the local HMI returns to the actual setting folder. If the
Log on has failed, then the Log on window opens again, until either the user makes
it right or presses “Cancel”.
15.1.3.1
Authorization with Central Account Management enabled IED
GUID-1A836989-5D89-4F3D-B3A2-3BABCDFFB440 v1
The users, their roles and rights are created, deleted and edited only in the Central
Account Management server (SDM600). However, the user rights can be edited in
the IED by using the PCM600 user tool.
Section 15
1MRK 505 384-UEN A
Security
630
Breaker protection REQ650 2.2 IEC
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...