Name
Values (Range)
Unit
Step
Default
Description
StartPhSel
1 out of 3
2 out of 3
3 out of 3
-
-
1 out of 3
Number of phases required for op (1 of
3, 2 of 3, 3 of 3)
DirMode1
Off
Non-directional
Forward
Reverse
-
-
Non-directional
Directional mode of step 1 (off, nodir,
forward, reverse)
Characterist1
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
-
-
ANSI Def. Time
Selection of time delay curve type for
step 1
I1>
5 - 2500
%IB
1
1000
Operating phase current level for step 1
in % of IBase
t1
0.000 - 60.000
s
0.001
0.000
Def time delay or add time delay for
inverse char of step 1
k1
0.05 - 999.00
-
0.01
0.05
Time multiplier for the inverse time delay
for step 1
IMin1
1 - 10000
%IB
1
100
Minimum operate current for step1 in %
of IBase
t1Min
0.000 - 60.000
s
0.001
0.000
Minimum operate time for inverse curves
for step 1
I1Mult
1.0 - 10.0
-
0.1
2.0
Multiplier for current operate level for
step 1
DirMode2
Off
Non-directional
Forward
Reverse
-
-
Non-directional
Directional mode of step 2 (off, nodir,
forward, reverse)
Table continues on next page
Section 6
1MRK 505 384-UEN A
Current protection
88
Breaker protection REQ650 2.2 IEC
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...