![Subaru impreza 2017 Owner'S Manual Download Page 134](http://html.mh-extra.com/html/subaru/impreza-2017/impreza-2017_owners-manual_1389064134.webp)
PID-4151-OUTPUTSIGNALS v4
Table 61:
NS4PTOC Output signals
Name
Type
Description
TRIP
BOOLEAN
General trip signal
TR1
BOOLEAN
Trip signal from step 1
TR2
BOOLEAN
Trip signal from step 2
TR3
BOOLEAN
Trip signal from step 3
TR4
BOOLEAN
Trip signal from step 4
START
BOOLEAN
General start signal
ST1
BOOLEAN
Start signal step 1
ST2
BOOLEAN
Start signal step 2
ST3
BOOLEAN
Start signal step 3
ST4
BOOLEAN
Start signal step 4
STFW
BOOLEAN
Forward directional start signal
STRV
BOOLEAN
Reverse directional start signal
6.5.5
Settings
PID-4151-SETTINGS v4
Table 62:
NS4PTOC Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
EnDir
Disable
Enable
-
-
Enable
Enabling the Directional calculation
AngleRCA
-180 - 180
Deg
1
65
Relay characteristic angle (RCA)
UPolMin
1 - 100
%UB
1
5
Minimum voltage level for polarization in
% of UBase
I2>Dir
1 - 100
%IB
1
10
Residual current level in % of IBase for
Direction release
DirMode1
Off
Non-directional
Forward
Reverse
-
-
Non-directional
Directional mode of step 1 (off, nodir,
forward, reverse)
Table continues on next page
Section 6
1MRK 505 384-UEN A
Current protection
128
Breaker protection REQ650 2.2 IEC
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...