![Subaru impreza 2017 Owner'S Manual Download Page 137](http://html.mh-extra.com/html/subaru/impreza-2017/impreza-2017_owners-manual_1389064137.webp)
Name
Values (Range)
Unit
Step
Default
Description
Characterist4
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
-
-
ANSI Def. Time
Time delay characteristic for step 4
I2-4>
1 - 2500
%IB
1
17
Negative sequence current op level for
step 4 in % of IBase
t4
0.000 - 60.000
s
0.001
1.200
Time delay of step 4 when definite time
char. is selected
k4
0.05 - 999.00
-
0.01
0.05
Time multiplier for the step 4 selected
time characteristic
IMin4
1.00 - 10000.00
%IB
1.00
17
Minimum current for step 4
t4Min
0.000 - 60.000
s
0.001
0.000
Minimum operate time for inverse time
characteristic step 4
I4Mult
1.0 - 10.0
-
0.1
2.0
Multiplier for scaling the current setting
value for step 4
Table 63:
NS4PTOC Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
ResetTypeCrv1
Instantaneous
IEC Reset
ANSI reset
-
-
Instantaneous
Reset curve type for step1
(Instantaneous / IEC / ANSI)
tReset1
0.000 - 60.000
s
0.001
0.020
Reset time delay for step 1
tPCrv1
0.005 - 3.000
-
0.001
1.000
Param P for customized inverse trip time
curve for step 1
tACrv1
0.005 - 200.000
-
0.001
13.500
Param A for customized inverse trip time
curve for step 1
tBCrv1
0.00 - 20.00
-
0.01
0.00
Param B for customized inverse trip time
curve for step 1
tCCrv1
0.1 - 10.0
-
0.1
1.0
Param C for customized inverse trip time
curve for step 1
tPRCrv1
0.005 - 3.000
-
0.001
0.500
Param PR for customized inverse reset
time curve for step 1
tTRCrv1
0.005 - 100.000
-
0.001
13.500
Param TR for customized inverse reset
time curve for step
tCRCrv1
0.1 - 10.0
-
0.1
1.0
Param CR for customized inverse reset
time curve for step 1
Table continues on next page
1MRK 505 384-UEN A
Section 6
Current protection
Breaker protection REQ650 2.2 IEC
131
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...