IEC05000133-3-en.vsd
tMin
Current
Operate
time
IMin
IEC05000133 V2 EN-US
Figure 338:
Minimum time-lag operation for the IEC curves
In order to fully comply with IEC curves definition setting parameter tMin shall be
set to the value which is equal to the operating time of the selected IEC inverse
time curve for measured current of twenty times the set current start value. Note
that the operating time value is dependent on the selected setting value for time
multiplier k.
In addition to the ANSI and IEC standardized characteristics, there are also two
additional inverse curves available; the RI curve and the RD curve.
The RI inverse time curve emulates the characteristic of the electromechanical
ASEA relay RI. The curve is described by equation
:
[ ]
0.339 0.235
=
>
-
×
æ
ö
ç
÷
ç
÷
ç
÷
è
ø
k
t s
in
i
EQUATION1194 V1 EN-US
(Equation 65)
where:
in>
is the set start current for step n
k
is set time multiplier for step n
i
is the measured current
Section 20
1MRK 505 384-UEN A
Inverse time characteristics
738
Breaker protection REQ650 2.2 IEC
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...