Upper limit for measured currents, active/reactive-power is 2.4 times rated value.
Upper limit for measured voltages and frequency is 1.2 times rated value.
The upper limit is the maximum value that can be encoded into the ASDU
(Application Service Data Unit). Any value higher than this value will be tagged as
OVERFLOW. The factors 1.2 and 2.4 are taken from the 103 standard and require
that a rated value to use as base exists, and then use 1.2 or 2.4 times <rated> as
maxVal
. You can use 2.4 times rated as
maxVal
, but as there is no way to propagate
value to client, the use of a scale factor on <rated> does not make much difference.
You can configure client:
client-scaled-max ::= 1.2 * <rated>
or
client-scaled-max ::= 1.0 * <maxVal>
If the client has a hard-coded gain of 1.2 * <rated> then
client-scaled-
max ::= 1.2 times <maxVal>/1.2
Resolution is <maxVal> / 4095 and hence the lowest possible
maxVal
yields the
best accuracy.
Table 477:
I103MEAS supported indications
INF
Description
148
IL1
144, 145,
146, 148
IL2
148
IL3
147
IN, Neutral current
148
UL1
148
UL2
148
UL3
145, 146
UL1-UL2
147
UN, Neutral voltage
146, 148
P, active power
146, 148
Q, reactive power
148
f, frequency
Measurands in private range, I103MEASUSR
M11874-431 v5
Number of instances: 3
Function type parameter for each block in private range.
Information number must be selected for measurands.
1MRK 505 384-UEN A
Section 14
Station communication
Breaker protection REQ650 2.2 IEC
615
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...