![Subaru impreza 2017 Owner'S Manual Download Page 493](http://html.mh-extra.com/html/subaru/impreza-2017/impreza-2017_owners-manual_1389064493.webp)
11.10
Running hour-meter TEILGAPC
11.10.1
Identification
GUID-3F9EF4FA-74FA-4D1D-88A0-E948B722B64F v1
Function Description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2 device
number
Running hour-meter
TEILGAPC
-
-
11.10.2
Functionality
GUID-464FB24F-B367-446C-963A-A14841943B87 v2
The Running hour-meter (TEILGAPC) function is a function that accumulates the
elapsed time when a given binary signal has been high, see also figure
.
Time Accumulation
with Retain
BLOCK
ACC_HOUR
RESET
IN
tWarning
tAlarm
OVERFLOW
WARNING
ALARM
q
-1
a>b
a
b
a>b
a
b
a>b
a
b
&
&
&
q
-1
= unit delay
IEC15000321-1-en.vsd
ACC_DAY
99 999.9 h
tAddToTime
ADDTIME
IEC15000321 V1 EN-US
Figure 233:
TEILGAPC logics
The main features of TEILGAPC are:
•
Applicable to very long time accumulation (≤ 99999.9 hours)
•
Supervision of limit transgression conditions and rollover/overflow
•
Possibility to define a warning and alarm with the resolution of 0.1 hours
•
Retain any saved accumulation value at a restart
•
Possibilities for blocking and reset
•
Possibility for manual addition of accumulated time
•
Reporting of the accumulated time
1MRK 505 384-UEN A
Section 11
Monitoring
Breaker protection REQ650 2.2 IEC
487
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...