a
b
a>b
BLOCK
AND
I
OP
Extract second
harmonic current
component
Extract
fundamental
current component
X
2ndHarmStab
a
b
a>b
a
b
a>b
0.07*IBase
IEC13000015-4-en.vsdx
UseStartValue
IN1>
IN2>
IN3>
IN4>
a
b
a>b
t
t=70ms
OR
AND
BlkParTransf=On
q
-1
OR
2ndH_BLOCK_Int
q
-1
= unit delay
IEC13000015 V4 EN-US
Figure 46:
Simplified logic diagram for 2nd harmonic blocking feature and Block for Parallel Transformers
feature
6.4.7.10
Switch on to fault feature
M13941-211 v5
Integrated in the four step residual overcurrent protection are the switch on to fault
logic (SOTF) and the under-time logic. The setting parameter
SOTF
is set to
activate SOTF, the under-time logic or both. When the circuit breaker is closing
there is a risk to close it onto a permanent fault, for example during an
autoreclosing sequence. The SOTF logic will enable fast fault clearance during
such situations. The time during which SOTF and under-time logics will be active
after activation is defined by the setting parameter
t4U
.
The SOTF logic uses the start signal from step 2 or step 3 for its operation, selected
by setting parameter
StepForSOTF
. The setting parameter
ActivationSOTF
can be
set for activation of CB position open change, CB position closed change or CB
close command. In case of a residual current start from step 2 or 3 (dependent on
1MRK 505 384-UEN A
Section 6
Current protection
Breaker protection REQ650 2.2 IEC
123
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...