10.7.6
Pulse timer function block PULSETIMER
IP11016-1 v2
M11466-3 v3
The pulse (PULSETIMER) function can be used, for example, for pulse extensions
or limiting the operation time of outputs. The PULSETIMER has a settable length.
When the input is 1, the output will be 1 for the time set by the time delay
parameter
t
. Then it returns to 0.
10.7.6.1
Function block
M11465-3 v4
PULSETIMER
INPUT
OUT
IEC04000407-3-en.vsd
IEC04000407 V3 EN-US
Figure 174:
PULSETIMER function block
10.7.6.2
Signals
PID-6985-INPUTSIGNALS v1
Table 238:
PULSETIMER Input signals
Name
Type
Default
Description
INPUT
BOOLEAN
0
Input to pulse timer
PID-6985-OUTPUTSIGNALS v1
Table 239:
PULSETIMER Output signals
Name
Type
Description
OUT
BOOLEAN
Output from pulse timer
10.7.6.3
Settings
PID-6985-SETTINGS v1
Table 240:
PULSETIMER Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
t
0.000 - 90000.000
s
0.001
0.010
Time delay of function
10.7.6.4
Technical data
GUID-E05E5FB1-23E7-4816-84F2-1FBFFDFF2B43 v1
Table 241:
Number of PULSETIMER instances
Logic block
Quantity with cycle time Range or Value
Accuracy
3 ms
8 ms
100 ms
PULSETIMER
10
10
20
(0.000–90000.000) s
±0.5% ±10 ms
1MRK 505 384-UEN A
Section 10
Logic
Breaker protection REQ650 2.2 IEC
359
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...