PID-4144-OUTPUTSIGNALS v6
Table 356:
BINSTATREP Output signals
Name
Type
Description
OUTPUT1
BOOLEAN
Logical status report output 1
OUTPUT2
BOOLEAN
Logical status report output 2
OUTPUT3
BOOLEAN
Logical status report output 3
OUTPUT4
BOOLEAN
Logical status report output 4
OUTPUT5
BOOLEAN
Logical status report output 5
OUTPUT6
BOOLEAN
Logical status report output 6
OUTPUT7
BOOLEAN
Logical status report output 7
OUTPUT8
BOOLEAN
Logical status report output 8
OUTPUT9
BOOLEAN
Logical status report output 9
OUTPUT10
BOOLEAN
Logical status report output 10
OUTPUT11
BOOLEAN
Logical status report output 11
OUTPUT12
BOOLEAN
Logical status report output 12
OUTPUT13
BOOLEAN
Logical status report output 13
OUTPUT14
BOOLEAN
Logical status report output 14
OUTPUT15
BOOLEAN
Logical status report output 15
OUTPUT16
BOOLEAN
Logical status report output 16
11.7.5
Settings
PID-4144-SETTINGS v6
Table 357:
BINSTATREP Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
t
0.0 - 60.0
s
0.1
10.0
Time delay of function
11.7.6
Operation principle
GUID-537921CA-82B9-4A02-BAD1-67E3AC61AE96 v3
The Logical signal status report (BINSTATREP) function has 16 inputs and 16
outputs. The output status follows the inputs and can be read from the local HMI or
via SPA communication.
When an input is set, the respective output is set for a user defined time. If the
input signal remains set for a longer period, the output will remain set until the
input signal resets.
Section 11
1MRK 505 384-UEN A
Monitoring
480
Breaker protection REQ650 2.2 IEC
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...