supervision element and the integrated directional comparison
function.
The protection has an integrated directional feature. As the operating quantity
current I
op
is always used, the polarizing method is determined by the parameter
setting
polMethod
. The polarizing quantity will be selected by the function in one
of the following three ways:
1. When
polMethod
=
Voltage
, UPol will be used as polarizing quantity.
2. When
polMethod
=
Current
, IPol will be used as polarizing quantity.
3. When
polMethod
=
Dual
, UPol + IPol · ZNPol will be used as polarizing
quantity.
The operating and polarizing quantity are then used inside the directional element,
as shown in Figure
, in order to determine the direction of the earth fault.
STRV
0.6 * IN>DIR
STFW
-RCA -85 deg
40% of
IN>DIR
IN>DIR
RCA
65°
U = -3U
pol 0
I = 3I
op 0
RCA +85 deg
RCA -85 deg
Characteristic
for STRV
Operating area
Operating area
Characteristic
for STFW
Characteristic for reverse
release of measuring steps
Characteristic for forward
release of measuring steps
-RCA +85 deg
IEC11000243-1-en.ai
IEC11000243 V1 EN-US
Figure 44:
Operating characteristic for earth-fault directional element using
the zero sequence components
The relevant setting parameters for the directional supervision element are:
1MRK 505 384-UEN A
Section 6
Current protection
Breaker protection REQ650 2.2 IEC
119
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...