16.11
Primary system values PRIMVAL
16.11.1
Identification
GUID-B8B3535D-227B-4151-9E98-BEB85F4D54DE v1
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Primary system values
PRIMVAL
-
-
16.11.2
Functionality
M15288-3 v6
The rated system frequency and phase rotation direction are set under
Main menu/
Configuration/ Power system/ Primary Values
in the local HMI and PCM600
parameter setting tree.
16.11.3
Settings
PID-1626-SETTINGS v17
Table 537:
PRIMVAL Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Frequency
50.0 - 60.0
Hz
10.0
50.0
Rated system frequency
PhaseRotation
Normal=L1L2L3
Inverse=L3L2L1
-
-
Normal=L1L2L3
System phase rotation
Section 16
1MRK 505 384-UEN A
Basic IED functions
676
Breaker protection REQ650 2.2 IEC
Technical manual