11.10.3
Function block
GUID-D0E9688B-C9D9-44B7-BD95-81132CCA5E4F v1
TEILGAPC
BLOCK
IN
ADDTIME
RESET
ALARM
WARNING
OVERFLOW
ACC_HOUR
ACC_DAY
IEC15000323.vsdx
IEC15000323 V1 EN-US
Figure 234:
TEILGAPC function block
11.10.4
Signals
PID-6998-INPUTSIGNALS v1
Table 366:
TEILGAPC Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Freeze the accumulation and block the outputs
IN
BOOLEAN
0
The input signal that is used to measure the
elapsed time, when its value is high
ADDTIME
BOOLEAN
0
Add time to the accumulation
RESET
BOOLEAN
0
Reset accumulated time
PID-6998-OUTPUTSIGNALS v1
Table 367:
TEILGAPC Output signals
Name
Type
Description
ALARM
BOOLEAN
Indicator that accumulated time has reached
alarm limit
WARNING
BOOLEAN
Indicator that accumulated time has reached
warning limit
OVERFLOW
BOOLEAN
Indicator that accumulated time has reached
overflow limit
ACC_HOUR
REAL
Accumulated time in hours
ACC_DAY
REAL
Accumulated time in days
11.10.5
Settings
PID-6998-SETTINGS v1
Table 368:
TEILGAPC Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
tAlarm
1.0 - 99999.9
Hour
0.1
90000.0
Time limit for alarm supervision
tWarning
1.0 - 99999.9
Hour
0.1
50000.0
Time limit for warning supervision
tAddToTime
0.0 - 99999.9
Hour
0.1
0.0
Time to add to the accumulation
Section 11
1MRK 505 384-UEN A
Monitoring
488
Breaker protection REQ650 2.2 IEC
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...