Making capacity at resistive load
0.2 s
1.0 s
30 A
10 A
220–250 V/0.4 A
110–125 V/0.4 A
48–60 V/0.2 A
24–30 V/0.1 A
Breaking capacity for AC, cos
j
> 0.4
250 V/8.0 A
250 V/8.0 A
Breaking capacity for DC with
L/R < 40 ms
48 V/1 A
110 V/0.4 A
220 V/0.2 A
250 V/0.15 A
48 V/1 A
110 V/0.4 A
220 V/0.2 A
250 V/0.15 A
Maximum capacitive load
-
10 nF
17.2.10
Serial and LON communication module (SLM)
IP15583-1 v2
17.2.10.1
Introduction
M14933-3 v5
The Serial and LON communication module (SLM) is used for SPA, IEC
60870-5-103, DNP3 and LON communication. SLM has two optical
communication ports for plastic/plastic, plastic/glass or glass/glass fibre cables.
One port is used for serial communication (SPA, IEC 60870-5-103 or DNP3 port)
and the other port is used for LON communication.
17.2.10.2
Design
M17126-3 v6
SLM is a PMC card and it is factory mounted as a mezzanine card on the first
Analog digital conversion module (ADM). Three variants of SLM are available
with different combinations of optical fiber connectors, see figure
fiber connectors are of snap-in type and the glass fiber connectors are of ST type.
1MRK 505 384-UEN A
Section 17
IED hardware
Breaker protection REQ650 2.2 IEC
705
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...