PID-6915-OUTPUTSIGNALS v4
Table 47:
EFPIOC Output signals
Name
Type
Description
TRIP
BOOLEAN
Trip signal
6.3.5
Settings
IP11449-1 v2
PID-6915-SETTINGS v4
Table 48:
EFPIOC Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
IN>>
5 - 2500
%IB
1
200
Operate residual current level in % of
IBase
Table 49:
EFPIOC Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
IN>>Min
5 - 2500
%IB
1
5
Minimum used operate residual current
level in % of IBase, if IN>> is less than
IN>>Min then IN>> is set to IN>>Min
IN>>Max
5 - 2500
%IB
1
2500
Maximum used operate residual current
level in % of IBase, if IN>> is greater
than IN>>Max then IN>> is set to
IN>>Max
StValMult
0.5 - 5.0
-
0.1
1.0
Multiplier for operate current level
Table 50:
EFPIOC Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base
Value groups
6.3.6
Monitored data
PID-6915-MONITOREDDATA v4
Table 51:
EFPIOC Monitored data
Name
Type
Values (Range)
Unit
Description
IN
REAL
-
A
Residual current
6.3.7
Operation principle
M12704-3 v8
The sampled analog residual currents are pre-processed in a discrete Fourier filter
(DFT) block. From the fundamental frequency components of the residual current,
as well as from the sample values the equivalent RMS value is derived. This
Section 6
1MRK 505 384-UEN A
Current protection
102
Breaker protection REQ650 2.2 IEC
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...