UAmpComp30
-10.000 - 10.000
%
0.001
0.000
Amplitude factor to calibrate voltage at
30% of Ur
UAmpComp100
-10.000 - 10.000
%
0.001
0.000
Amplitude factor to calibrate voltage at
100% of Ur
IAmpComp5
-10.000 - 10.000
%
0.001
0.000
Amplitude factor to calibrate current at
5% of Ir
IAmpComp30
-10.000 - 10.000
%
0.001
0.000
Amplitude factor to calibrate current at
30% of Ir
IAmpComp100
-10.000 - 10.000
%
0.001
0.000
Amplitude factor to calibrate current at
100% of Ir
IAngComp5
-10.000 - 10.000
Deg
0.001
0.000
Angle calibration for current at 5% of Ir
IAngComp30
-10.000 - 10.000
Deg
0.001
0.000
Angle calibration for current at 30% of Ir
IAngComp100
-10.000 - 10.000
Deg
0.001
0.000
Angle calibration for current at 100% of Ir
PID-6735-SETTINGS v3
Table 304:
CMMXU Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
IL1DbRepInt
1 - 100000
Type
1
10
Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
Operation
Off
On
-
-
Off
Operation Mode On / Off
IL1Min
0.0 - 500.0
%IB
0.1
50.0
Minimum value in % of IBase
IL1Max
0.0 - 500.0
%IB
0.1
200.0
Maximum value in % of IBase
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base
Value groups
IL1RepTyp
Cyclic
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
-
-
Cyclic
Reporting type
IL1AngDbRepInt
1 - 100000
s
1
10
Cyclic report interval (s)
IL2DbRepInt
1 - 100000
Type
1
10
Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
IL2Min
0.0 - 500.0
%IB
0.1
50.0
Minimum value in % of IBase
IL2Max
0.0 - 500.0
%IB
0.1
200.0
Maximum value in % of IBase
IL2RepTyp
Cyclic
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
-
-
Cyclic
Reporting type
IL2AngDbRepInt
1 - 100000
s
1
10
Cyclic report interval (s)
IL3DbRepInt
1 - 100000
Type
1
10
Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
IL3Min
0.0 - 500.0
%IB
0.1
50.0
Minimum value in % of IBase
Table continues on next page
Section 11
1MRK 505 384-UEN A
Monitoring
402
Breaker protection REQ650 2.2 IEC
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...