Activating
signal
LED
IEC01000228_2_en.vsd
IEC01000228 V2 EN-US
Figure 15:
Operating Sequence 1 (Follow-S)
GUID-107FE952-3B4C-4C01-831A-3147E652327C v4
If inputs for two or more colors are active at the same time to the same LED, the
priority color it shows is in accordance with the color described above. An example
of the operation when two colors are activated in parallel to the same LED is
shown in figure
.
Activating
signal GREEN
LED
IEC09000312_1_en.vsd
G
R
G
G
Activating
signal RED
IEC09000312 V1 EN-US
Figure 16:
Operating sequence 1, two colors
Sequence 2
(Follow-F)
SEMOD56072-47 v2
This sequence is the same as
Sequence 1
, Follow-S, but the LEDs are flashing
instead of showing steady light.
Sequence 3
LatchedAck-F-S
SEMOD56072-50 v2
This sequence has a latched function and works in collecting mode. Every LED is
independent of the other LEDs in its operation. At the activation of the input signal,
the indication starts flashing. After acknowledgment the indication disappears if
the signal is not present any more. If the signal is still present after
acknowledgment it gets a steady light.
Activating
signal
LED
Acknow.
en01000231.vsd
IEC01000231 V1 EN-US
Figure 17:
Operating Sequence 3 LatchedAck-F-S
GUID-CC607709-5344-4C88-AA97-6395FD335E55 v5
1MRK 505 384-UEN A
Section 5
Local Human-Machine-Interface LHMI
Breaker protection REQ650 2.2 IEC
73
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...