Table 562:
IOM - Binary input/output module contact data (reference standard: IEC 61810-2)
Function or quantity
Trip and signal relays
Fast signal relays (parallel reed
relay)
Binary outputs
10
2
Max system voltage
250 V AC, DC
250 V DC
Test voltage across open contact,
1 min
1000 V rms
800 V DC
Current carrying capacity
Per relay, continuous
Per relay, 1 s
Per process connector pin,
continuous
8 A
10 A
12 A
8 A
10 A
12 A
Making capacity at inductive load
with L/R > 10 ms
0.2 s
1.0 s
30 A
10 A
0.4 A
0.4 A
Making capacity at resistive load
0.2 s
1.0 s
30 A
10 A
220–250 V/0.4 A
110–125 V/0.4 A
48–60 V/0.2 A
24–30 V/0.1 A
Breaking capacity for AC, cos φ >
0.4
250 V/8.0 A
250 V/8.0 A
Breaking capacity for DC with L/R
< 40 ms
48 V/1 A
110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A
48 V/1 A
110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A
Maximum capacitive load
-
10 nF
M12584-1 v7
Table 563:
IOM with MOV and IOM 220/250 V, 110mA - contact data (reference standard: IEC
61810-2)
Function or quantity
Trip and Signal relays
Fast signal relays (parallel
reed relay)
Binary outputs
IOM: 10
IOM: 2
Max system voltage
250 V AC, DC
250 V DC
Test voltage across open
contact, 1 min
250 V rms
250 V rms
Current carrying capacity
Per relay, continuous
Per relay, 1 s
Per process connector pin,
continuous
8 A
10 A
12 A
8 A
10 A
12 A
Making capacity at inductive
loadwith L/R > 10 ms
0.2 s
1.0 s
30 A
10 A
0.4 A
0.4 A
Table continues on next page
Section 17
1MRK 505 384-UEN A
IED hardware
704
Breaker protection REQ650 2.2 IEC
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...