Operating
7.3 Relays
HydroRanger 200 HMI
102
Operating Instructions, 06/2018, A5E36281317-AC
Reservoir 2
Pump up with the following level and rate settings:
Parameter
Relay #
1
2
3
4
5
6
(Page 195)
Alternate Duty
Assist
Alternate Duty
Assist
Level (H)
Level (L)
OFF
OFF
(Page 197)
20%
20%
90%
10%
--
--
(Page 197)
80%
80%
85%
15%
--
--
(Page 198)
ON
Pump by Rate (2.8.1.8.) (Page 198)sets the pump relays to accept control by rate of level change
once the first ON setpoint is reached. Because the pumps are started by rate, you must change Fill-
ing Indicator (2.3.9.) (Page 176) to desired fill rate.
Summary of Contents for HydroRanger 200 HMI
Page 2: ......
Page 24: ...Safety notes HydroRanger 200 HMI 22 Operating Instructions 06 2018 A5E36281317 AC ...
Page 354: ...Updating software HydroRanger 200 HMI 352 Operating Instructions 06 2018 A5E36281317 AC ...
Page 362: ......
Page 403: ......